Cummins Onan QG gasoline generator fault codes (HGJAA, HGJAB, HGJBB)
Every fault code, display message, and status light listed in Onan's manuals and support pages for HGJAA / HGJAB / HGJAC and HGJBB operator manuals; HGJAA / HGJAB / HGJAC (QG 5500/7000 EFI) operator manuals; HGJAA / HGJAB / HGJAC Spec A-E. Select a code for what it means, what you can safely check, and when to call a technician.
Confirm your model
Codes are model-specific. Match the model number on the appliance data label to one of these before using the table:
HGJBB Spec A-B, HGJAA Spec J-K, HGJAB Spec J-L, QG RV generator, HGJAA Spec A-E, HGJAB Spec A-E, HGJAC Spec A-D, QG 5500/7000 EFI
Where to look and what to record
- generator model/spec letter
- hour meter
- fault blink count
- loads running when the shutdown occurred
- oil level and oil type noted after shutdown
Code table
| Code | What the manufacturer says | Listed for |
|---|---|---|
| 2 | Low Oil Pressure | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 3 | Service Check | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 4 | Over Crank | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 12 | Over Voltage | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 13 | Under Voltage | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 14 | Over Frequency | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 15 | Under Frequency | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 19 | Governor Actuator | HGJAA / HGJAB / HGJAC (QG 5500/7000 EFI) operator manuals |
| 22 | Governor Actuator Overload | HGJAA / HGJAB / HGJAC (QG 5500/7000 EFI) operator manuals |
| 23 | Low Oil Pressure Cutoff Switch | HGJAA / HGJAB / HGJAC Spec A-E |
| 27 | Voltage Sense | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 29 | High Battery Voltage | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 31 | Over Speed | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 32 | Low Cranking Speed | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 35 | Control Card Failure | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 36 | Engine Stopped | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 37 | Invalid Generator Set Configuration | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 38 | Over Current (Field Overload) | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 41 | Generator Rotor | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 42 | Processor | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 43 | Processor | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 45 | Speed Sense | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 47 | Ignition | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 48 | Generator Field Sense | HGJAA / HGJAB / HGJAC and HGJBB operator manuals |
| 51 | Processor | HGJAA / HGJAB / HGJAC (QG 5500/7000 EFI) operator manuals |
| 52 | Fuel Injector | HGJAA / HGJAB / HGJAC (QG 5500/7000 EFI) operator manuals |
| 54 | MAT Sender | HGJAA / HGJAB / HGJAC (QG 5500/7000 EFI) operator manuals |
| 56 | MAP Sender | HGJAA / HGJAB / HGJAC (QG 5500/7000 EFI) operator manuals |
| 57 | Over Prime | HGJAA / HGJAB / HGJAC (QG 5500/7000 EFI) operator manuals |
| 58 | Exhaust Gas Temperature Shutdown | HGJAA / HGJAB / HGJAC (QG 5500/7000 EFI) operator manuals |
| 81 | Exhaust Gas Temperature Sensor Open | HGJAA / HGJAB / HGJAC (QG 5500/7000 EFI) operator manuals |
| 82 | Exhaust Gas Temperature Sensor Shorted | HGJAA / HGJAB / HGJAC (QG 5500/7000 EFI) operator manuals |
Generators can produce carbon monoxide, moving-part hazards, fuel hazards, and lethal voltage. Shut the generator down and do not open energized compartments unless qualified.
Troubleshooting guides
- Onan generator stopped and shows a fault code
- Onan EC-AGS+ generator does not run A/C
- Onan generator exhaust smell, CO detector, or ventilation shutdown
- Onan generator fuel, oil, and maintenance checks before starting
- Onan generator high-altitude derating and fewer appliances
- Onan generator low battery or slow cranking
- Onan generator no-start cranking delay or overcrank
- Onan generator running but no output or breaker/load problem
- RV appliance low-voltage warning